CFN III Quick Reference
Page 54 MDE-4483 CFN III Quick Reference Guide v3.3 · August 2005
EECO tank monitor
Interface with CFN II or CFN3 using either the a
RS232 connection utilizing the CFN System’s PORT
command or a Gasboy RS232-RS485 converter. In
the EECO monitor setup menus, there are two
selections for connecting to a site controller. These
are:
Gasboy-PC or Gasboy-Site Control.
Gasboy-PC
Use this setting when connecting to one of the site’s
RS232 ports and interfacing using the PORT
command. This sets the communication parameters to
9600, odd, 1 stop bit, 7 data bits, and no security
code.
Gasboy-Site Control
Use this setting when connecting to one of the site's
RS485 loops. This sets the communication
parameters to 9600, odd, 1 stop bit, 7 data bits, and
security code to 000001. These parameters can also
be changed individually. You need a C07476 cable to
connect from the monitor to the 485/232 converter
(C05897).
Gasboy Interface Software
EECO SYSTEM™ 2000
Software
Minimum Revision
028 E
029 E
030 D
041 D
042 A
074 F
EECO SYSTEM™ 1500
Software
Minimum Revision
023 M
087 B
083 E
EECO SYSTEM™ Galaxy
Software
Minimum Revision
063 H
075 L
RS-422/485
Communications
422/485 Line Monitor
PC Monitor
There are no switches on the PC-based monitor. (DIP
Switch Banks 2 and 3, discussed below, apply only to
Site Controller I-based monitors.) PC monitors
require an RS 422/485 - RS232 converter, discussed
below after DIP switch banks.
Help. Press H for help on the PC.
DIP Switch Banks 2 and 3
These switches apply only to Site Controller I-based
monitors. Set these switches according to the speed
of the terminal to be hooked to the line monitor.
Local Terminal Baud Rate
Baud Rate 3-1 3-2 2-8
300 closed closed ----
1200 closed open ----
2400 open closed closed
4800 open closed open
9600 open open ----
RS-422/485 Port Baud Rate
DIP switch 3, positions 5-8, all open=9600 baud.
DIP switch 2, position 7, open=7 bits; closed=8 bits.
422/485-232 Converter
For PC monitors, Veeder-Root tank gauges, and
Profit Points. Part number: C05897.
Jumpers
Position 1 is top and position 2 is bottom when the
board is oriented so that GASBOY RS422/485-
RS232 CONVERTER is readable.
Position 1, both jumpers on upper two rows:
Position 2, both jumpers on lower two rows: