8 UNITEC Interface SCIII
Gasboy CFN Series
The RS485 cross cable is a 1x3, 2x4 cable such as C04500, used for
connecting the Current Loop Interface to the Site Controller. The RS422
cable should be a null modem or printer cable, depending on how your PC
COMM ports are set up.
3. Power up the SDI box.
4. Set SWA-7 DOWN and SWA-8 DOWN. Set all other switches UP.
5. Set SWA-8 UP.
6. Give the command:
BOOTSDI SDI.S19 1
or
BOOTSDI SDI.S19 2
depending on whether the SDI is connected to COM1 or COM2.
7. The SDI LED should blink rapidly and somewhat irregularly, for duration
of the download.
8. BOOTSDI should print a line of dots, and then say:
sdi.s19 successful
Done.
If so, go to step 9.
9. If BOOTSDI, after several seconds, says:
no sync from SDI, enter=retry, q=quit >
You may close SWA-8 again momentarily, then open it, press ENTER, and
return to step 6.
10. When you have received the “Done” message, set SWA-8 CLOSED.
11. Immediately set SWA-7 OPEN.
12. Immediately set SWA-8 OPEN and the SDI will go to run mode. This should
be signaled by regular on-off blink of the LED, a little faster than 30
blinks/minute.
Booting SDI from Site III
You will need the SCIII hardware diagnostics program DIAG.BIN. For this file to operate
properly it must be stored in C:\SC3\DIAG.BIN. You must also have the SDI operating
system must be stored in C:\SC3\XBIN\SDI.HEX.
1. At the console, enter the command: REBOOT;A DIAG to load the hardware
diagnostics.
2. Power up the SDI box.
3. Set SWA-7 DOWN and SWA-8 DOWN. Set all other switches UP.
4. Set SWA-8 UP.
5. After these steps have been completed, give the command ‘L’ which causes
the SDI download. You can have one SCI being downloaded on each loop
for a maximum of three. On the status line for the loop(s) that have a
download proceeding you should see progress of the download indicated.
If a failure is reported, check the cabling, do steps 2-5 again, then type ‘L’
again and proceed.
6. When you receive the “Loaded Successfully” message, set SWA-8 CLOSED.
7. Immediately set SWA-7 OPEN.
8. Next, set SWA-8 OPEN and the SDI will go to run mode. This should be