Removal and Installation Instructions
Page 4 MDE-4527 Gasboy Cold Weather External Filter Field Upgrade Kit • October 2005
Removal and Installation Instructions
TOP VIEW
TOP VIEW
1
2 3
Nipple extends
past side panel
or
Parts In Kit
Item No. Part Number Qty. Description
1 025903 1 Filter Adapter 2” CIM-TEK 420 (revision D or later)
2 025900 2 Filter Element CIM-TEK 800-10 (standard)
3 025901 2 Filter Element CIM-TEK HS10 (hydro)
not shown M06450B001 2 Filter Gasket (cold weather fluorosilicone) CIM-TEK 90546
1 Ensure power to unit has been removed and locked out.
2 Release any residual pressure through the hose nozzle into an approved container.
3 Place approved catch pan and absorbent material to catch any fuel.
4 Wearing safety goggles, carefully remove existing filter adapter. Save piping for reuse.
5 Remove and discard black gaskets that come with come with the filters.
6 Install new filter adapter (P/N 025903, rev D or later) onto piping using UL approved gas and
oil resistant pipe compound on male threads only.
Note: Placing pipe compound on female threads can force compound into piping and possibly
cause a malfunction of the equipment.
7 Install filter elements (PN/ 0259000 or P/N 0259001) using the blue fluorosilicone gaskets
(M06450B001) in the kit.